Standard Home Inspection Report
Client(s): Sample Report
Property address: Westinspect Eubank Inspections
Accurate Independent Inspections
Home - Commercial - Environmental
Inspection date: 2010
This report published on Monday, May 17, 2010 3:06:05 PM MDT

Property ownership is both a privilege and a responsibility. Take time to read the entire report. Westinspect Eubank Inspections will be glad to answer your questions after you have read the whole report, from beginning to end.

What is the purpose of this property inspection?


 
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
REPAIR or REPLACERecommend repairing or replacing 
REPAIR or MAINTAINRecommend repair and/or maintenance 
MINOR DEFECT or FUTURE REPAIRRecommend correction, but not urgent 
MAINTAINRecommend ongoing maintenance 
EVALUATERecommend evaluation by a specialist 
SERVICEABLEItem or component is in serviceable condition 
COMMENTFor your information 

Click here for a glossary of building construction terms.

  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General information
Exterior
Roof
Garage
Attic
Electric service
Water heater
Heating and cooling
Plumbing and laundry
Fireplaces, woodstoves and chimneys
Basement
Bathrooms
Interior rooms
Additional recommendations & information
 
General information Return to table of contents
Report number: 9086p
Type of building: Single family
Present during inspection: Clients, Property owners
Occupied: Yes
Weather conditions: Partly cloudy
Temperature: Warm
Ground condition: Dry
Front of structure faces: East
Foundation type: Finished basement
The following items are excluded from this inspection: Irrigation system, Air filtration in garage
 
Exterior Return to table of contents
Foundation material: Poured in place concrete
Wall covering: Composition wood clapboard, Brick veneer
Driveway material: Poured in place concrete
1) The driveway had significant cracks and/or deterioration in the southeast corner. Recommend repairing or replacing this section of driveway. Other minor cracks were noted, and many had been repaired with caulk. Recommend repairing all minor cracks with concrete caulk or similar product. See photo 2    
2) The downspout extension at the southeast corner of the house was ineffective, due to being located between two confining fence sections. This will prevent water from flowing freely away from the house, and can result in water accumulating around the structure's foundation. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. Repairs should be made as necessary, such as installing or repositioning splash blocks, or installing and/or repairing tie-ins to underground drain lines, so rain water is carried at least several feet away from the structure to soil that slopes down and away from the structure. See photo 3    
3) Three window wells below ground level did not have covers. This can allow water to penetrate to the foundation or basement. Recommend installing window well covers on all window wells. If window is located at a room that will be used as a bedroom, then also recommend installing hinges and a standard window well ladder, so that the window well can be used as a fire escape. See photo 4    
4) This home was clad with composition wood fiber siding. Some areas of siding on this structure showed symptoms of swelling, cracking, or delamination, but it appeared that the siding had not deteriorated to the point of needing replacement. Some manufacturers (Louisiana Pacific) recommend a repair process for this siding where affected areas are sealed with "Permanizer Plus", a flexible primer made by Pittsburgh Paint, followed by two coats of 100% acrylic latex paint. This sealant must be applied to the bottom edges using a brush. The face of the siding can be sprayed. The "Permanizer Plus" sealer isn't required for edges that aren't swollen, cracked or deteriorated, but the acrylic latex should still be brushed on these edges. At a minimum, recommend having a qualified contractor seal and repaint as described above, or by other methods specified by the siding's manufacturer. See photo 5    
5) Random gaps were found between sections of siding. Gaps should be sealed or caulked as necessary to prevent moisture intrusion and entry by vermin. See photo 6    
6) One downspout terminated above roof surfaces rather than being routed to gutters below or to the ground level. This is very common, but it can reduce the life of roof surface materials below due to large amounts of water frequently flowing over the roof surface. Granules typically are washed off of composition shingles as a result, and leaks may occur. Recommend considering having a qualified contractor install extensions as necessary so downspouts don't terminate above roof surfaces. See photo 8    
7) A plastic bag was wrapped around the driveway light. The seller reported that the bag keeps barn swallows from nesting in that fixture. See photo 7    
 
Roof Return to table of contents
Roof inspection method: Traversed
Roof covering: Asphalt or fiberglass composition shingles
Roof ventilation: Adequate
8) Debris had accumulated in one or more gutters. This is a conducive condition for wood destroying insects since gutters may overflow and cause water to come in contact with the structure's exterior or make water accumulate around the foundation. Gutters should be cleaned now and as necessary in the future.
9) Recommend resealing around all four skylights with roofing caulk, as a standard precaution to avoid water intrusion. See line 25 below. See photo 9    See photo 10    
10) A small area of deterioration was found on the soffit of the upper level on the west side. This appeared to be from a previous roof leak, and was not a current concern. The current roof had no leak evidence at the time of this inspection. No action is recommended at this time. See photo 11    
 
Garage Return to table of contents

11) The automatic door closing device (sprung hinges, etc.) on the garage-house door needs adjustment, repair or replacing. The door did not close and latch easily and/or completely via the force of the automatic closing device. This door is intended to prevent vehicle fumes from entering living spaces and to slow the spread of fire from the garage to living spaces. A qualified contractor should evaluate and make repairs as necessary.
12) The vehicle door had an electric opener installed, and the manual lock mechanism on the door had not been disabled. Damage or injury may occur if the vehicle door opener is operated with the manual lock engaged. A qualified contractor should disable or remove the lock mechanism. For more information on garage door safety issues, visit: http://www.cpsc.gov/cpscpub/pubs/523.html or http://www.ohdstl.com/safety.html See photo 13    
13) Much of the garage, include areas around the interior perimeter and in the center are excluded from this inspection due to lack of access from stored items.
 
Attic Return to table of contents
Inspection method: Viewed from hatch
Insulation material: Fiberglass loose fill
Insulation depth: 9 inches average
Insulation estimated R value: R-23 by calculation
14) The ceiling insulation's R rating was slightly less than R-30 which is recommended for this area. Recommend having a qualified contractor install additional insulation as per standard building practices for better energy efficiency.
 
Electric service Return to table of contents
Primary service type: Underground
Primary service overload protection type: Circuit breakers
Service amperage (amps): 125
Location of main service switch: Panel on back wall of basement utility room
Location of main disconnect: Top right
Service entrance conductor material: Aluminum
Branch circuit wiring type: Copper
Solid strand aluminum branch circuit wiring present: No
Smoke detectors present: Yes
15) One screw was missing from the cover of the electric service panel. Recommend replacing this screw so that panel cover completely protects the enclosed wiring. Stock screws from the panel manufacturer should be used, or their equivalent.
16) No concerns were found with the overall electrical system at the time of this inspection.
 
Water heater Return to table of contents
Estimated age: 10 years (1998)
Type: Tank
Energy source: Natural gas
Capacity (in gallons): 50
Manufacturer: Kenmore
Model: Power Miser 10
17) The estimated useful life for most water heaters is 8 to 12 years. This water heater appeared to be approaching this age and may need replacing at any time. Recommend budgeting for a replacement in the future.
 
Heating and cooling Return to table of contents
Primary heating system energy source: Natural gas
Primary heat system type: Forced air
Primary Air conditioning type: Rooftop evaporative cooler
Distribution system: Sheet metal ducts
Manufacturer: Lennox (two units)
18) The filters for the heating systems should be checked monthly and replaced or washed as necessary.
19) The last service date of these systems appeared to be more than one year ago, or the inspector was unable to determine the last service date. The clients should ask the property owner when they were last serviced. If unable to determine the last service date, or if these systems were serviced more than one year ago, a qualified heating and cooling contractor should inspect, clean, and service these systems, and make repairs if necessary. For safety reasons, and because these systems are fueled by gas or oil, this servicing should be performed annually in the future. The brief visual observation by the home inspector is NOT a substitute for the complete servicing that is recommended here. For more information visit: http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html
20) No concerns were found with the heating and cooling systems at the time of this inspection. See photo 12    
 
Plumbing and laundry Return to table of contents
Location of main water shut-off valve: Back wall of basement utility room
Location of main water meter: Southeast corner of front yard, near driveway
Location of main fuel shut-off: Gas meter on north side of house
Water service: Public
Supply pipe material: Copper
Drain pipe material: Plastic
21) No concerns were found with the overall plumbing system at the time of this inspection.
 
Fireplaces, woodstoves and chimneys Return to table of contents
Fireplace type: Metal prefabricated
Chimney type: Masonry
22) This gas-log fireplace was operated by a remote control, and was working properly at the time of this inspection.
 
Basement Return to table of contents
Pier or support post material: Steel
Beam material: Steel
Floor structure above: Engineered wood joists
 
Bathrooms Return to table of contents

23) Upstairs bathroom with a shower did not have an exhaust fan installed. Moisture accumulation will occur and may damage the structure. Even if the bathroom has a window that opens, it likely does not provide adequate ventilation, especially during cold weather when the window is closed. A qualified contractor should install exhaust fans as per standard building practices where missing in bathrooms with showers.
24) Basement shower handle was difficult to operate, requiring a lot of force to turn on and off. Recommend replacing this shower handle.
 
Interior rooms Return to table of contents

25) The skylight in the small front bathroom (near the front entry) showed evidence of past leaking. Paint was bubbled and soft in two small areas, and a thicker layer of caulk was noted around the interior edges of the skylight. Recommend sealing around the exterior of this skylight. See line 9 above. Recommend occasional monitoring to make sure skylight does not leak during heavy rain or snow.
26) This structure was built in 1979 and may contain lead paint. Laws were enacted in 1978 in the US preventing the use of lead paint in residential structures. Lead is a known safety hazard, especially to children but also to adults. The paint found in and around this structure appeared to be intact and may be encapsulated by more recent layers of paint that are not lead-based. Regardless, recommend following precautions as described in the following links to Consumer Products Safety Commission website articles regarding possible lead paint.

What You Should Know About Lead Based Paint in Your Home: Safety Alert - CPSC Document #5054

CPSC Warns About Hazards of "Do lt Yourself" Removal of Lead Based Paint: Safety Alert - CPSC Document #5055
 
Additional recommendations & information Return to table of contents

27) This house meets the following requirements as required in HUD Handbooks 4905.1 and 4150.2: The house can be used and maintained individually without trespass on adjoining properties. It has independent utilities. It has safe and potable water. It has sanitary facilities with a safe method of sewage disposal. The heating is adequate for healthful and comfortable living conditions. The house has domestic hot water. It has electricity for lighting and for equipment used in the living unit. The property has vehicular or pedestrian access from a public or private street. Access to the house is provided without passing through any other living unit. There is no evidence of continuing settlement, leakage, termites, excessive dampness, decay, or other conditions impairing safety or sanitation of the dwelling.
28) OLDER HOME: We expect homes to be built according to the standard practices and building codes, if any, that were in use at the date of construction. Older homes often have areas or systems that do not comply with current building codes. While this Inspection makes every effort to point out safety concerns, it does not inspect for building code compliance.

It is common for homes of any age to have had repairs done, and some repairs may appear less than standard. This Inspection looks for items that are not functioning as intended. It does not grade the quality of the repairs.

In older homes, the Inspector reviewed the structure from the standpoint of how it has fared through the years with the materials that were used. You can expect problems to become apparent as time passes. The Inspector will not be able to find all deficiencies in and around a property, especially concerning construction techniques of the past.

29) PUEBLO: For Pueblo City and County map information, see the Pueblo County Geographic Information System (GIS) at http://www.gis.co.pueblo.co.us/.

For contractor searches, building codes, permits, and building reports, see the Pueblo Regional Building Department at http://www.prbd.com/.

For Pueblo City government, see http://www.pueblo.us/.

For local health and environmental issues, see the Pueblo City-County Health Department at http://www.co.pueblo.co.us/pcchd/.

For septic system information in Pueblo County, see http://www.co.pueblo.co.us/pcchd/environmental/isds/index.php

30) Photos are included to help you better understand the condition of the property at the time of the inspection. Photos are intended to show an example of a concern, but they may not show every occurence and may not accurately show its severity. Not every concern will have a photo. Do not rely on photos alone.
31) Material defect is a condition with a real property or any portion of it that would have a significant adverse impact on the value of the real property or that involves an unreasonable risk to people on the property. The fact that a structural element, system or subsystem is near, at or beyond the end of the normal useful life of such a structural element, system or subsystem is not by itself a material defect.
 

Photo 1  
Eubank Inspections Sample Report 2008

Photo 2  
driveway deterioration

Photo 3  
downspout between two fence sections

Photo 4  
window wells

Photo 5  
deterioration at lower edge of siding

Photo 6  
gaps between siding pieces

Photo 7  
plastic wrap at driveway light

Photo 8  
downspout above roof

Photo 9  
front skylight

Photo 10  
back skylight

Photo 11  
minor deterioration of soffit on back side

Photo 12  
rooftop evaporative cooler

Photo 13  
lock not disabled on garage door
 

 
©Copyright 2010 Westinspect Eubank Inspections. This Report is the exclusive property of this Inspection company and the client(s) listed in the Report title. Use of this Report by any unauthorized persons is prohibited.

This Report has been prepared according to the Standards of Practice of the International Association of Certified Home Inspectors. In your inspection report, the emphasis is on visible structural conditions. Decor choices, decorative fixtures, furniture and personal items are not included in a standard home inspection.

Limitations apply to this Report. See the standard home inspection agreement.

Answers to many of your common questions can be found at Frequently Asked Questions.

POLICIES: Privacy Policy, Payment Policy, Recourse Policy and Business Principles can all be found at the Policies page.

SNAPSHOT: Your Inspection is like a "snapshot" of the property's condition on a specific date and time. Those conditions will change, so you need to keep inspecting your property during the time you own it:
Verify that any air conditioning condensate water is draining properly to the exterior after operation on a hot day.
Verify that the dryer vent is exhausting properly.
Verify that the gutters and downspouts are performing during a hard rain.
Verify that no water is ponding on the property after a hard rain.
Verify that no dimming or flickering of lights occurs.
Verify that no repeated resetting of any circuit breakers is necessary.
Verify that the quantity of the hot water supply is adequate.
Verify that the performance of the HVAC systems are adequate.
Verify that no leaking is present in the attic area during a hard rain.
And inspect any of the other concerns that were mentioned in this Report.

Have you read the complete report? It provides safety and maintenance information, as well as common concerns and ways to solve those concerns. If you have any questions about the report, please call or e-mail me. Also visit the website at www.westinspect.us.

EXPIRATION DATE: Your Inspection Report describes the property's condition on the day of the Inspection. Conditions can change daily due to ongoing use, deferred maintenance, and environmental circumstances. Your inspection follow-up service expires 60 days after the inspection date. If you do not purchase this property, then this Report expires on the date that the purchase contract expires or is canceled. If you like, you may allow others to read your Report as a part of your informed decision-making. You are not authorized to pass your Report on to other potential buyers, or to other real estate agents.